CB-7080 & CB-7080D Counter/Timer User's Guide @AASA(data)
2-49
@AASA(data)
Description: Set the Hi-Hi alarm limit of counter 0 (for alarm-mode 1). Refer to "Counter alarm mode
selection" for more information.
Syntax: @AASA(data)[chk](cr)
@ A delimiter character
AA 2-character HEX module address, from 00 to FF
SA
(data) 8-character HEX value.
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Response:
Valid response !AA[chk](cr)
Invalid response ?AA[chk](cr)
no response Syntax error, communication error or address error
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Examples:
The Hi-Hi alarm limit of counter 0 is FFFF0000h:
command: @01SAFFFF0000(cr)
response: !01(cr)
The Hi-Hi alarm limit of counter 0 is 0000FFFFh:
command: @02SA0000FFFF(cr)
response: !02(cr)