CB-7080 & CB-7080D Counter/Timer User's Guide @AADO0D
2-38
@AADO0D
Description: Set digital output.
Syntax: @AADO0D[chk](cr)
@ A delimiter character
AA 2-character HEX module address, from 00 to FF
DO0
D=0 D/O0=D/O1=OFF
D=1 D/O0=ON, D/O1=OFF
D=2 D/O0=OFF, D/O1=ON
D=3 D/O0=D/O1=ON
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Response:
Valid response !AA[chk](cr)
Invalid response ?AA[chk](cr)
alarm is enabled ?AA[chk](cr)
no response Syntax error, communication error or address error
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
[chk] 2-character checksum. If checksum is disabled no [chk]
(cr) 0x0D
Examples:
Turn all D/O OFF:
command: @01DO00(cr)
response: !01(cr)
Turn D/O ON; Turn D/O 1 OFF:
command: @02DO01(cr)
response: !02(cr)
Note:
If the alarm is enabled, D/O 0 and D/O 1 will always be controlled by the module. Therefore the following
D/O conditions will exist:
- Power-on value is changed to hi/lo condition immediately.
- The @AADO0D command is ignored.