Measurement-computing PointScan 300 Series rev.1.0 Bedienungsanleitung Seite 27

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 42
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 26
PointScan/300 Users Manual
9-12-01
Discrete Output Modules 5-5
PointScan/336
Dry Contact Relay Module
This discrete output module has six Form C relay output channels that switch DC or AC power to the field
devices. The current rating for each output channel is 0.1 mA to 2 amps DC, or 0.1 mA to 500 mA (0.5A)
AC. Screw terminals, compatible only with the universal wiring base, are provided for the normally closed
and normally open outputs.
Watchdog Output Feature
The first DC output channel may be configured (using the Remote IO Toolkit program) as a watchdog
output. If this feature is selected, the output will be on when there is good command activity from the
gateway.
Seitenansicht 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 41 42

Kommentare zu diesen Handbüchern

Keine Kommentare