Measurement-computing CB-COM-7021 Bedienungsanleitung Seite 57

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 76
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 56
57
CB-7021, CB-7022, CB-7024 Users Manual
2.24 $AA9NTS
Description: Set DA Configuration of Channel N
Note: The command is for CB-7022 only.
Syntax: $AA9NTS[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
9 Command for setting DA configuration
N Channel to set DA configuration (0 to 1)
T Analog output type. Refer Sec. 1.10 for type select
S Analog output slew rate. Refer Sec. 1.10 for slew rate
select
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $019121 Receive: !01
Set address 01 channel 1 DA configuration: 0 to 10V output
and slew rate 0.625V/Second, returns successful.
Related Command:
Sec. 2.23 $AA9N
Seitenansicht 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 75 76

Kommentare zu diesen Handbüchern

Keine Kommentare