Measurement-computing CB-COM-7012 Bedienungsanleitung Seite 26

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 72
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 25
26
CB-7012, CB-7014, CB-7017 Users Manual
2.3 #AA
Description: Read Analog Input
Syntax: #AA[CHK](cr)
# Delimiter character
AA Address of module (00 to FF)
Response: Valid Command: >(Data)[CHK](cr)
Syntax or communication error may get no response.
> Delimiter for valid command
(Data) Analog input value, reference Sec. 1.10 for its format
When using #AA command to CB-7017/17F, the data is
the combination for each channel respectively.
Example:
Command: #01 Receive: >+02.635
Read Address 01, get data successful.
Command: #02 Receive: >4C53
Read Address 02, get data in HEX format successfully.
Command: #04
Receive: >+05.123+04.153+07.234-02.356+10.000-
05.133+02.345+08.234
The module Address 04 is CB-7017. Read Address 04 to
get data from all eight channels.
Related Command:
Sec. 2.1, %AANNTTCCFF; Sec. 2.7, $AA2
Related Topics:
Sec. 1.10, Configuration Tables