This bit is set when in REP_ENB mode, and the Sample
Counter has reached terminal count.
REP_DONE0
This bit is set when in REP_ENB mode and the FIFO is
half-full.
REP_FLG1
This bit is set when in REP_ENB mode and the FIFO
has been overrun. This flag indicates that the FIFO is
being loaded too quickly
OVERRUN2
This bit is set when in REP_ENB mode and the FIFO
has been underrun. This flag indicates that the FIFO is
being unloaded too quickly.
UNDERRUN3
1=Interrupt Pending, 0 = No InterruptIRQ7
DescriptionNameBit
5.2.9 FIFO Clear Start Address Register
This is a write only register. A write to this register clears the FIFO address pointers to
zero. Data is don’t care. Prior to initiating a REP-STRING transfer the FIFO write and
read address pointers should always be cleared to a start address of 0.
Base Address + Bh
XXXXXXXX
01234567
MSB LSB
5.2.10 REP String Control Register
This is a read/write register. These bits are in the inactive reset state after power-up.
Base Address + Ch
xx
ERR_ENBDBL_
BUFF
HALF_
FF_CNT
REP_
CONT
REP_
ENB
REP_
MODE
01234567
MSB LSB