6K-SSR-RACK08 User's Guide Installing the 6K-SSR-RACK08
Figure 2-7
Figure 2-7. Relay logic jumpers JP5 and JP6
shows SSR modules 1-4 set to invert logic (active high), and modules 5-8 set to non-invert logic
(active low).
JP5
3
NON-INVERT
21
INVERT
SSR modules 1-4
configured for active high
JP6
3
NON-INVERT
21
INVERT
SSR modules 5-8
configured for active low
The I/O type and the relay logic settings control what happens when a module activates. For example, a module
group configured for SSR input with non-inverted logic outputs a low logic level when the module is ON. A
module group configured for SSR output with non-inverted logic requires a low logic level to turn the output
module ON.
2-11